C H A P T E R  3

Facility and System Requirements


3.1 Facility Power Requirements

To prevent catastrophic failures, the design of the power system must ensure that adequate power is provided to your Sun Fire E25K/E20K systems. Sun Microsystems suggests that all power circuits supplying power to the Sun Fire E25K/E20K systems be derived from dedicated electrical distribution panels. Electrical work and installations must comply with applicable local, state, or national electrical codes.



caution icon

Caution - System earth fault protection relies on the building circuit.



Sun Microsystems makes every effort to minimize the effects of power failures and interruptions to the hardware. The Sun Fire E25K/E20K systems have dual, redundant, current-sharing power supply inputs, and are designed to use two independent power sources. However, if the computer equipment is subjected to repeated power interruptions and fluctuations, it is susceptible to a higher component failure rate than it would be with a stable power source. Provide a stable power source, such as an uninterruptible power system (UPS), to reduce the possibility of component failures.

The power supplies of the Sun Fire E25K/E20K systems incorporate an inrush current limitation after the first power on. The maximum inrush current is 50 amps peak, during hot or cold start (after the AC has been removed for 60 seconds) and 30 amps RMS, hot or cold, when measured over one line cycle. The inrush current decays to its normal operating current in less than 200 ms.

Every Sun Fire E25K/E20K system cabinet and customer selected I/O expansion rack requires its own customer-supplied circuit breakers and receptacles. Ensure the power receptacles are within 14 ft (427 cm cable length) of the system cabinet and each customer selected I/O expansion rack location.

TABLE 3-1 lists the electrical specifications for the system cabinet or customer selected I/O expansion rack. See FIGURE 3-1, FIGURE 3-2, and FIGURE 3-3 for illustrations of the possible system power connections. Use TABLE 3-2 to record the power cable requirements (see Appendix A for an expanded form to use and retain for your records). TABLE 3-3 provides a summary of features of the three power configurations.

TABLE 3-1 Facility Power Requirements

Electrical Service

Specification

System and I/O expansion racks require:

Voltage

200-240 VAC, single phase

Power factor

.99

Frequency

47-63 Hz

Circuit breaker : North America and Japan

Circuit breaker: International

Twelve 30A

Twelve 32A

Current drawn

23,760 VA (Max Load)

Power cords (15 ft maximum)

15 ft (457 cm) connector-compatible drop cord

Receptacle: North America and Japan
Receptacle: International P/N 180-1944-01

NEMA L6-30R or equivalent
IEC 309, single phase, 32A


 

TABLE 3-2 Facility Power Cable Requirements Worksheet

Frame Type

Number of Cabinets

 

Number of Poles

 

Number * of Cords

 

Single Phase

3 Phase

System Cabinet (Single Phase)

____

x

2

x

__

=

____

n/a

Total number of poles required

 

 

 


* Contact a Sun Microsystems System Engineer for power cord quantity information when choosing the proper number of power cords needed for your system configuration.

 FIGURE 3-1 Sun Fire E25K/E20K Systems Power Connections--Redundant Power, Double Power Source (Power Source A and B)

Figure showing the system power connections for redundant power (double power source).[ D ]

 FIGURE 3-2 Sun Fire E25K/E20K Systems Power Connections--High-Reliability Power, Single Power Source (One Power Source)

Figure showing the system power connections for high-reliability power using a single power source.[ D ]

 FIGURE 3-3 Sun Fire E25K/E20K Systems Power Connections--Basic Single Power, Single Power Source (One Power Source, No Redundancy, Not Advisable)

Figure showing the system power connections for basic single power (no redundancy, not advisable).[ D ]

 

TABLE 3-3 Power Configuration Summary

Configuration

Protection From Loss of Internal Power Supply

Protection From Loss of External Source of Power

Redundant (FIGURE 3-1)

Yes

Yes, one of two sources

High reliability (FIGURE 3-2)

Yes

No, only one source

Basic (FIGURE 3-3)

Yes

No, only one source



3.2 Cabinet Grounding Requirements

The Sun Fire E25K/E20K systems achieve earth ground through the power cords. For this reason, a grounding cable is not provided with the system. The power cords have three prongs: two for current and one for ground. At the AC input module, the ground prong and system chassis are connected. Final chassis ground is achieved when the power cord is connected to a receptacle, where the ground prong contacts the power receptacle. For successful grounding, the customer must provide properly grounded power receptacles so the power distribution unit (PDU) ground is earth ground.

A ground cable may be affixed to the system. While not required, the additional ground point allows leakage current to dissipate more efficiently. It is important to note that power cords are grounded through the receptacle and the ground cable must reference a common earth ground. Otherwise, a difference in ground potential can be introduced.



caution icon

Caution - If the customer is unsure of the facility PDU receptacle grounding, do not install a ground cable until a proper PDU receptacle grounding has been confirmed. If a difference in ground potential is apparent, corrective action must be taken.



Use the following procedures to properly ground the Sun Fire E25K/E20K systems.



Note - You can use the A-series circuit breaker (Carlingswitch, part number: AF3-X0-06-184-X13-D, or equivalent) if a PDU is used between the Sun Fire E25K/E20K systems and the facility power system.



 

1. Ensure the customer has properly grounded PDUs in the data center. The PDU must be earth ground.

2. Ensure all grounding points (raised floors and power receptacles) reference PDU ground.



Note - The customer needs to procure the grounding cable. A grounding cable is not shipped with the system.



3. Attach the ground cable to the system, behind the kick plate, at the bottom of the frame base as shown in FIGURE 3-4.

 FIGURE 3-4 Ground Cable Attachment Point at System Cabinet

Figure showing the system ground cable-attachment point at the base of the cabinet.

4. The ground cable attaching area might be a painted surface. Ensure metal-to-metal solid contact is made for this installation.