Sun Fire V60x Compute Grid Rack System Installation Guide
|
|
This appendix contains product specifications, organized into the following sections:
Power Specifications
The following table lists the system power specifications.
TABLE A-1 Sun Fire V60x Compute Grid Power Specifications
Parameter
|
Value
|
Nominal voltage
|
200, 208, 220, 230, or 240 VAC
|
Operating voltage
|
Single-phase 180 to 240 VAC
|
Frequency
|
47 to 63 Hz
|
Current
|
Maximum 64Amps (4 x 16Amps)
Nominal 40Amps(4 x 10Amps), fully populated rack
|
AC plug
|
NEMA L6-20P Domestic U.S.A.
IEC 309 16A 3-position International
|
AC plugs required
|
Four AC plugs required per rack
|
Physical Dimensions
The following table lists the physical dimensions of the system.
TABLE A-2 Sun Fire V60x Compute Grid Physical Dimensions
Parameter
|
value
|
Dimensions
|
74 inches height x 23.5 in. width x 35.4 in. depth
(188 centimeters height x 60 cm width x 90 cm depth)
|
Weight (fully populated rack)
|
1600 pounds
(727 kilograms)
|
Rack units
|
38
|
Single rack unit dimensions
|
1.75 inches height x 19 in. width x 23.6 in. depth
(4.45 centimeters height x 48.26 cm width x 60 cm depth)
|
Environmental Requirements
This section contains the environmental requirements for a fully-populated, single-rack Sun Fire V60x Compute Grid rack system. The requirements are described in two separate tables for the 2.8-GHz CPU Compute Grid rack system and the
3.06-GHz CPU Compute Grid rack system. Refer to either of the following two tables:
- TABLE A-3, 2.8-GHz CPU Compute Grid Environmental Specifications
- TABLE A-4, 3.06-GHz CPU Compute Grid Environmental Specifications
TABLE A-3 2.8 GHz CPU Sun Fire V60x Compute Grid Environmental Specifications
Parameter
|
Operating
|
Non-Operating
|
Temperature
|
86°F maximum ambient temperature at 0 feet elevation
(30°C maximum ambient temperature at 0 meters elevation)
|
-40°F to 158°F
(-40°C to 65°C)
|
Altitude
|
Up to 9000 feet, maximum ambient temperature derated by 1.8°F per 1500 feet rise in elevation above 0 feet.
(Up to 3000 meters, maximum ambient temperature derated by 1°C per 500 meter rise in elevation above 0 meters.)
|
Up to 35000 feet
(Up to 12000 meters)
|
Humidity
|
10% to 90% relative humidity at 80°F maximum wet bulb, non-condensing.
(10% to 90% relative humidity at 27°C maximum wet bulb, non-condensing.)
|
10% to 90% relative humidity
|
Vibration
|
.25 g's 5Hz to 500Hz to 5Hz,
1.0 octaves per minute,
swept-sine 5 sweeps in X, Y, and Z.
|
n/a
|
TABLE A-4 3.06 GHz CPU Sun Fire V60x Compute Grid Environmental Specifications
Parameter
|
Operating
|
Non-Operating
|
Temperature
|
77°F maximum ambient temperature at 0 feet elevation
(25°C maximum ambient temperature at 0 meters elevation)
|
-40°F to 158°F
(-40°C to 65°C)
|
Altitude
|
Up to 4500 feet, maximum ambient temperature derated by 1.8°F per 1000 feet rise in elevation above 0 feet.
(Up to 1500 meters, maximum ambient temperature derated by 1°C per 300 meter rise in elevation above 0 meters.)
|
Up to 35000 feet
(Up to 12000 meters)
|
Humidity
|
10% to 90% relative humidity at 80°F maximum wet bulb, non-condensing.
(10% to 90% relative humidity at 27°C maximum wet bulb, non-condensing.)
|
10% to 90% relative humidity
|
Vibration
|
.25 g's 5Hz to 500Hz to 5Hz,
1.0 octaves per minute,
swept-sine 5 sweeps in X, Y, and Z.
|
n/a
|
Sun Fire V60x Compute Grid Rack System Installation Guide
|
817-3072-10
|
|
Copyright © 2003, Sun Microsystems, Inc. All rights reserved.