A P P E N D I X  A

Product Specifications

This appendix contains product specifications, organized into the following sections:


Power Specifications

The following table lists the system power specifications.

TABLE A-1 Sun Fire V60x Compute Grid Power Specifications

Parameter

Value

Nominal voltage

200, 208, 220, 230, or 240 VAC

Operating voltage

Single-phase 180 to 240 VAC

Frequency

47 to 63 Hz

Current

Maximum 64Amps (4 x 16Amps)

Nominal 40Amps(4 x 10Amps), fully populated rack

AC plug

NEMA L6-20P Domestic U.S.A.

IEC 309 16A 3-position International

AC plugs required

Four AC plugs required per rack



Physical Dimensions

The following table lists the physical dimensions of the system.

TABLE A-2 Sun Fire V60x Compute Grid Physical Dimensions

Parameter

value

Dimensions

74 inches height x 23.5 in. width x 35.4 in. depth

(188 centimeters height x 60 cm width x 90 cm depth)

Weight (fully populated rack)

1600 pounds

(727 kilograms)

Rack units

38

Single rack unit dimensions

1.75 inches height x 19 in. width x 23.6 in. depth

(4.45 centimeters height x 48.26 cm width x 60 cm depth)



Environmental Requirements

This section contains the environmental requirements for a fully-populated, single-rack Sun Fire V60x Compute Grid rack system. The requirements are described in two separate tables for the 2.8-GHz CPU Compute Grid rack system and the
3.06-GHz CPU Compute Grid rack system. Refer to either of the following two tables:

 

TABLE A-3 2.8 GHz CPU Sun Fire V60x Compute Grid Environmental Specifications

Parameter

Operating

Non-Operating

Temperature

86°F maximum ambient temperature at 0 feet elevation

(30°C maximum ambient temperature at 0 meters elevation)

-40°F to 158°F

(-40°C to 65°C)

Altitude

Up to 9000 feet, maximum ambient temperature derated by 1.8°F per 1500 feet rise in elevation above 0 feet.

(Up to 3000 meters, maximum ambient temperature derated by 1°C per 500 meter rise in elevation above 0 meters.)

Up to 35000 feet

(Up to 12000 meters)

Humidity

10% to 90% relative humidity at 80°F maximum wet bulb, non-condensing.

(10% to 90% relative humidity at 27°C maximum wet bulb, non-condensing.)

10% to 90% relative humidity

Vibration

.25 g's 5Hz to 500Hz to 5Hz,
1.0 octaves per minute,

swept-sine 5 sweeps in X, Y, and Z.

n/a


 

TABLE A-4 3.06 GHz CPU Sun Fire V60x Compute Grid Environmental Specifications

Parameter

Operating

Non-Operating

Temperature

77°F maximum ambient temperature at 0 feet elevation

(25°C maximum ambient temperature at 0 meters elevation)

-40°F to 158°F

(-40°C to 65°C)

Altitude

Up to 4500 feet, maximum ambient temperature derated by 1.8°F per 1000 feet rise in elevation above 0 feet.

(Up to 1500 meters, maximum ambient temperature derated by 1°C per 300 meter rise in elevation above 0 meters.)

Up to 35000 feet

(Up to 12000 meters)

Humidity

10% to 90% relative humidity at 80°F maximum wet bulb, non-condensing.

(10% to 90% relative humidity at 27°C maximum wet bulb, non-condensing.)

10% to 90% relative humidity

Vibration

.25 g's 5Hz to 500Hz to 5Hz,
1.0 octaves per minute,

swept-sine 5 sweeps in X, Y, and Z.

n/a